Go  
 Categories 
 Shopping cart 
Cart is Empty
 Info 
Contact Us
Privacy statement
Terms & Conditions
Tax & Shipping
Return Policy
 Authentication 
Email address

Password

     Log in      
     Register  
Recover password
Catalog > Shop by Price > Generators between $15,001 - $19,000 > Winco PSS40LS Packaged Standby Generator

Winco PSS40LS Packaged Standby Generator

Details:

The PSS40LS is equipped with a 6-cylinder OHV GM engine that can run off LP or NG. The engine generator combination has the ability to start and operate motors up to 17.5 HP code G. This generator is available in single-phase 120/240V and three-phase 120/208V, 120/240V, 277/480V.


Click here to print a brochure of this model.


Click here to print a brochure of the entire line.

Shipping: Price Includes Freight to a Business Address. The customer is responsible for unloading merchandise upon delivery.
 
Price:$ 17,291.00
 
Options:
 
Voltage (Choose One): 
Auto Transfer Switch: 
Auto Transfer Switch Enclosure: 
Vapor Fuel Strainer: 
LP Liquid Withdrawal (Non-UL): 
NFPA 110: 
Remote Annunciator: 
Battery Heater: 
 
Add to Cart  Add to Cart  



Specifications:


Winco PSS40LS Packaged Standby Generator

Price Includes Freight to a Business Address - The customer is responsible for unloading merchandise upon delivery.

Features and Specifications
 
Power Rating - Continuous Standby (Derate 3.5% per 1,000 feet elevation above sea level.)

  • Power Output (60 Hz) - -3 120/240 1-phase / 1.0 p.f.
    • LP Gas
      • 40.0 KW; 40.0 KVA; 167 Amps
    • Natural Gas
      • 40.0 KW; 40.0 KVA; 167 Amps
  • Mainline Circuit Breaker (Standard)
    • 175 amps / NG or LP
  • Power Output (60 Hz) - -4 120/208 3-phase / 1.0 p.f.
    • LP Gas
      • 40.0 KW; 50.0 KVA; 139 Amps
    • Natural Gas
      • 40.0 KW; 50.0 KVA; 139 Amps
  • Mainline Circuit Breaker (Standard)
    • 125 amps / NG or LP
  • Power Output (60 Hz) - -17 120/240 3-phase / 1.0 p.f.
    • LP Gas
      • 40.0 KW; 50.0 KVA; 120 Amps
    • Natural Gas
      • 40.0 KW; 50.0 KVA; 125 Amps
  • Mainline Circuit Breaker (Standard)
    • 125 amps / NG or LP
  • Power Output (60 Hz) - -18 277/480 3-phase / 1.0 p.f.
    • LP Gas
      • 40.0 KW; 50.0 KVA; 60 Amps
    • Natural Gas
      • 40.0 KW; 50.0 KVA; 60 Amps
  • Mainline Circuit Breaker (Standard)
    • 60 amps / NG or LP

Engine Specifications

  • Make / Model
    • GM 4.3L
  • Displacement
    • 262 cubic in. 
  • Rated Power (Derate 3.5% per 1,000 feet elevation above sea level.)
    • 61 HP
  • Engine Speed
    • 1800 rpm

Fuel Consumption

  • LP Gas (One gallon of L.P. gas equals 4.23 lbs.) / Full Load
    • 5.9 gallons / hour 
  • Natural Gas / Full Load
    • 499 feet3 / hour

Engine Features – Standard Features

  • Electronic Ignition
  • Engine Pre-heater
  • Vapor Fuel System
  • Critical Grade Exhaust Silencer
  • Battery Rack & Cables (Battery not included. Requires 12 Volt / BCI Group 24 / 650 CCA battery.)
  • Vibration Isolators
  • Cooling System
    • Liquid 
  • dB(A) Rating @ 7 Meters (23 feet)
    • 75 dBA Full Load
    • 70 dBA No Load

Control System – Standard Features

  • Auto-Off-Test-Switch
  • Over-speed Shutdown
  • Low Oil Protection
  • High Temperature Shutdown
  • A.C. Metering
  • Running Time Meter
  • Engine Gauges
  • Alarm Contacts
  • Voltage Adjustment
  • Battery Charger
  • Mainline Circuit Breaker

Generator Data

  • Generator Type (Rotating Field Brushless design)
    • RFL / XTR
  • Voltage Regulation
    • + / - 1%
  • Frequency Regulation (NL-FL)
    • + / - 5%
  • Motor Starting Ability (Code G capacitor start motor.)
    • 15 HP

Size and Weight

  • L x W x H (inches)
    • 81 x 35.5 x 49.75
  • Ship Weight (pounds)
    • 1920

Warranty Information

  • Engine
    • 3 years or 3500 hours
  • Generator
    • 1 year or 1000 hours

Optional Accessories

  • UL Listed ASCO Automatic Transfer Switch (165 Series) 200 amp -3 120/240 single phase - NEMA 1 enclosure (indoor) (3R optional).
  • UL Listed Asco Automatic Transfer Switch (300 Series) 200 amp -4 120/240; -17 120/208; -18 277/480 three phase - NEMA 1 enclosure standard (indoor) (3R optional).
  • Vapor Fuel Strainer

Designed to filter contaminants in the fuel. The contaminants range in the form of dirt and metal, water and air (vapor).  For all PSS models.

  • LP Liquid Withdrawal

With a liquid withdrawal system, the LP fuel is removed from the tank in liquid form and is brought to the generator set in a gaseous form. LP Liquid Withdrawal provides better operation in colder temperatures and can allow for a smaller capacity fuel tank. This item is Non-UL and should be approved by local code before ordering.

  • NFPA 110 Level 1 Compliant Upgrade (Factory Installed)

The National Fire Protection Association (NFPA) maintains several standards covering standby generators and automatic transfer switches (ATS). Level 1 is most stringent and imposed when failure of the standby system could result in loss of human life or serious injury making it a must for any health care facility.  For models PSS30LS & up (factory installed).

  • Remote Annunciator

Displays 7 pre-alarms and 8 alarm indicators to instantly alert staff of problems with the power system.  This panel complies with the requirements of NFPA 110. 

  • Battery Heater

This heater sits under the battery and encloses all four sides to ensure quick and easy starting in cold weather climates.  For PSS21LS & Up.

 

Winco PSS40LS

 
Web Design by a Minneapolis Web Design Company Affordable Web Design